Joint Circular issued by the Ministry of Manpower (MOM) and the Singapore Civil Defence Force (SCDF)
SAFE STORAGE AND HANDLING OF FLAMMABLE SUBSTANCES
Background
1 On 7 March 2023, an explosion followed by a fire occurred in a room that served a motor workshop, causing parts of the building’s walls to collapse. Investigations revealed that the fire was likely due to the ignition of accumulated flammable vapours from a waste oil collection tank within the room.
2 Days later, another fire incident occurred on 13 March 2023. The fire engulfed an industrial building and caused minor injuries to two workers. Investigations indicated that uncontrolled electrostatic discharge had ignited flammable vapours generated during a dispensing process. Both incidents were dangerous occurrences that could have caused fatalities.
Storage of Flammable Liquids
3 To prevent similar fires, occupiers shall ensure that flammable liquids are kept away from all sources of heat or ignition such as hot surfaces, open flames and even equipment that are not suitably enclosed to prevent internal sparks from igniting any flammables in the surrounding (see Annex A for examples); and stored in containers made of non-combustible materials of sound integrity, labelled, and covered to prevent accidental spills and accumulation of flammable vapours in the workplace (see Annex B for examples).
4 Effective controls shall also be implemented to mitigate electrostatic discharge. This includes the installation of grounding and bonding systems as well as the conduct of annual continuity tests, both by competent persons.
Management of Flammable Wastes
5 Flammable liquid wastes, such as petrol collected from vehicle repair/servicing activities, can cause fires and explosions. Motor workshop operators, for example, shall identify and ensure that liquid wastes containing such flammable liquids are stored separately from non-flammable liquid wastes, before collection by licenced toxic industrial waste collectors (TIWCs). Mixtures of flammable liquid waste and liquids shall be treated as flammable liquids unless they have been laboratory-tested as non-flammable and may therefore be subjected to licensing requirements by the SCDF
6 TIWCs licensed by National Environment Agency shall be engaged to dispose flammable liquid waste or mixtures. A list of TIWCs can be found here or via the QR code.
Other Control Measures to Prevent Fires and Explosions
7 There are other control measures for flammable substances that are required to prevent fires and explosions in the workplace. Occupiers can refer to the resources listed below, for information and practical guidance. Occupiers can also refer to SCDF’s website on Information of Petroleum and Flammable Material (P&FM) Storage Licence.
Resources
WSH Guidelines on Flammable Materials, published by the WSH Council
Environment Public Health (Toxic Industrial Waste) Regulations
Fire Safety Act and Fire Safety (Petroleum and Flammable Materials) Regulations
WSH (Risk Management) Regulations
SS 532: Code of Practice for the Storage of Flammable Liquids
SS 603: Code of Practice for Hazardous Waste Management
No comments: