Acetylene gas explosion kills worker |
On 30 December 2022,
two workers were checking and maintaining spent cylinders when an explosion
occurred. One worker was killed while the other worker was conveyed to the
hospital for smoke inhalation and subsequently discharged.
|
Scene of the accident. |
Spent gas cylinders
may contain significant amounts of remnant gas, which can cause death or
serious injuries when released. The WSH Council calls on all companies
storing or handling flammable gas cylinders to undertake an urgent assessment
of their safety measures. |
What companies should do |
Companies should
urgently assess and ensure that their WSH management system includes the
following measures or checks: |
● Safe remnant gas release: Discharge flammable gases from cylinders only
under safe conditions and after a thorough assessment of work and
environmental risks. Any release should be properly controlled. Flammable
gases should be discharged through vent lines to a safe location, with
control valves and flame arrestor as well as effective ventilation to prevent
build-up of a flammable mixture. ● Remove ignition
sources: Remove all potential
sources of ignition (e.g. open flames, frictional sparks, hot surfaces) from
the designated work area before discharging flammable gas. Bonding and
grounding may be necessary to reduce static discharge. Check electrical
outlets for overloading as well as electrical equipment for defective or
exposed wiring as these can cause overheating or produce sparks. |
● Safer equipment and tools: Use non-sparking tools when working with gas
cylinders containing flammables. Ensure that electrical equipment (including
work area lighting) used is rated explosion-proof. |
● Segregation of incompatible work: Check for incompatible work (e.g. hot work or
any work that generates sparks) nearby before discharging flammable gas. Do
not proceed with flammable gas discharge if there is incompatible work. ● Hazard
communication: Label
gas cylinders as per SS 586: Part 2: 2014 Specification for Hazard Communication for
Hazardous Chemicals and Dangerous Goods to warn of the hazards and precautions for proper storage
and handling. Brief workers on the risk controls in place and provide on-site
supervision to ensure the work is carried out safely. ● Personal protective
equipment: In addition to
fire-retardant coveralls, equip workers with personal gas detectors or
install fixed gas detectors within the work area where gas can accumulate to
alert workers to the build-up of a flammable mixture. |
For more information,
refer to WSH (General Provisions) Regulations, SS 639: 2018 Code of
Practice for the Filling, Inspection, Testing and Maintenance of Gas
Cylinders for the Storage and Transport of Compressed Gases: Part 3 Acetylene
Cylinders – Periodic Inspection and Maintenance, WSH Council’s Code of
Practice on WSH Risk Management, and WSH
Guidelines on Management of Hazardous Chemicals Programme. Refer
to the Safety Data Sheet for detailed information specific to acetylene. |
Under the WSH Act, first-time corporate offenders may be sentenced to the maximum fine of $500,000 whilst individuals can either be sentenced to the maximum fine of $200,000 and/or an imprisonment not exceeding 2 years. Read more on the WSH Act penalties from Singapore Ministry of Manpower Website
•
Debarment from hiring new work pass holders • Company
leaders to personally account to MOM and take responsibility for
rectifications • Engaging
external auditors to conduct a thorough review of company’s WSH processes |
No comments: